Estimated noise
Reached at from the source
Reached at from the source
How these figures are worked out
Level at distance r = enclosure level at 7 m + 10 × log10(number of generators) − 20 × log10(r ÷ 7). This assumes open ground with no screening, so it is a simple upper estimate close to the site. Beyond about 1 km, air absorption and buildings reduce levels, so those rings are shown dashed and are indicative only.
Enclosure levels: Jubaili Bros, generator noise control guidance (standard enclosures 70–75 dB(A) at 7 m; critical-grade 65 dB(A)). Generator numbers and testing (each generator tested individually: 5 minutes weekly, 1 hour monthly, 2 hours yearly): EIA scoping report for GLi's scheme (26/2370/EIA), sections 4.1 and 4.4. All generators run together only in a grid failure.
Cooling noise is continuous, 24 hours a day, but GLi has not published the number or type of cooling units, so it is not modelled here.